Chillquick Thermo? heat pumps (100...300 kW)

Model CHT-32...100-4D-X-P1-P3-STD, type and selections are available from Chiller Oy´s sales engineers or from an authorized sales organization.

Model CHT 32-4 44-4 48-4 64-4 80-4 100-4
Heating cap. kW 98,2 128,2 149,9 201,8 259,8 307,2
Cap. adjusting 0;25;50;100% 0;25;50;100% 0;25;50;100% 0;25;50;100% 0;25;50;100% 0;25;50;100%
Mains 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
Power input kW 52,6 67,6 77,0 105,0 128,0 151,5
Running amps A 89,3 114,9 138,4 174,4 224 255,2
Precut-out fuse A (slow) 100 125 160 200 250 315
Nominal flows:            
Cold side kg/s 4,89 6,32 7,42 9,80 13,0 15,6
Hot side kg/s 4,49 5,86 6,86 9,21 11,9 14,1
Refr. R410A kg 12,6 18 18 30 34 36
Dimensions:            
Length mm 2170 2170 2170 2170 2170 2170
Width mm 900 900 900 900 900 900
Height mm 1950 1950 1950 1950 1950 1950

 

Capacity by values 0/-3°C (30% etanol) and 44/50°C (water)
Power input: compressor and pumps P1 and P3
Exact selection data from sales engineer (on base of concrete project requirements)
Chiller Oy reserves right to make changes without prior notice!


Heat pumps - accesories

Brochure CHTAM100657ENA.pdf