| Technical data with refrigerant R-407C (DX-radiator) | ||
| AUC = upward blowing direct condensation | ||
| ADC = downward blowing direct condensation | ||
| Nominal chilling output at room temperature 24? C, 50 %, condensation temperature 45? C | ||
| Dual-circuit units | ||
| Device type | 130-2 | 140-2 |
| Total output kW | 50 | 58 |
| Sensible output kW | 46 | 49 |
| Chilling output requirement kW | 65 | 75 |
| Compressors (hermetic) 400V-3ph-50Hz | ||
| Number | 2 | 2 |
| Power requirement kW | 15 | 18 |
| Centrifugal fans 230V-1Ph-50Hz direct drive | ||
| Number | 3 | 3 |
| Air quantity m3/s | 3,18 | 3,18 |
| External pressure Pa | 60 | 60 |
| Motor output kW | 2,25 | 2,25 |
| Filters EU5 | ||
| Number | 3 | 3 |
| Size: upward blowing | 600x600 | 600x600 |
| Size: downward blowing | 560x650 | 560x650 |
| After-heating 400V-3Ph-50Hz | ||
| Heating output kW | 12 | 12 |
| Number of elements | 4 | 4 |
| Number of steps | 3 | 3 |
| Humidification 400V-3Ph-50Hz | ||
| Humidification output kg | 9,4 | 9,4 |
| Connected load kW | 6,9 | 6,9 |
| Dimensions and weight | ||
| Width mm | 2300 | 2300 |
| Depth mm | 650 | 650 |
| Height mm | 1920 | 1920 |
| Weight kg | 490 | 490 |
| Exhaust chamber height 500 mm | ||
| (to be added to height of unit, models AUC, WUC) | ||
| Connections | ||
| Humidifier mm | 6 | 6 |
| Drain mm | 32 | 32 |
| Unit´s electrical connected load 400V-3Ph-50Hz | ||
| Types A and E kW | 17,5 | 21,0 |
| Type B kW | 29,3 | 33,0 |
| Type C kW | 24,2 | 27,9 |
| Type D kW | 36,2 | 39,9 |
| Condenser selections | ||
| AUC and ADC units | ||
| Device type | 130-2 | 140-2 |
| Condensing output requirement kW | 65 | 75 |
| Condensers (outdoor temperature 30°C, condensation temperature 45°C) | ||
| Alternative 1 | CCS 13-9 | CCS 14-9 |
| Noise level dB(A) at 10-m distance | 48 | 49 |
| Alternative 2 | CCS 11-14 | CCS 12-14 |
| Noise level dB(A) at 10-m distance | 60 | 58 |